4/0, 4/0, & 4/0 Underground Secondary Distribution Cable

Color:
Black.

Description:
Underground Secondary Distribution Cables are twisted assemblies of alloy 1350 aluminum conductors insulated with cross-linked polyethylene. They are used in various underground applications in secondary distribution circuits.

Conductor:
Compressed Class B compressed stranded, 1350 series aluminum alloy.

Insulation:
Black cross-linked polyethylene (XLPE)

Assembly:
Phase conductors and neutral conductors are cabled together to form a twisted assembly.

Applicable Standards:
- UL 854: Service ENtrance Cables
- ICEA S-105-692 Standard for 600 Volt Single Layer Thermoset Insulated Utility Underground Distribution Cables

4/0, 4/0, & 4/0 Triplex URD Cable Specifications*:

Phase Conductor Size: 4/0
Phase Conductor Insulation Thickness: 0.080 inches
Neutral Conductor Size: 4/0
Neutral Conductor Insulation Thickness: 0.080 inches
Outside Diameter: 1.457 inches
Weight: 0.828 lbs per ft
Allowable Ampacity-Direct Burial: 315 Amps
Allowable Ampacity-In Duct: 240 Amps

*Data provided on this page is subject to change based on different manufacturers variances.